Approvals
Q45AD9(a)(b),
Q459E(b)
a = Sensing mode D, DL, F, FP, FV, LV, LP, CV, CV4 or R.
b = Connecon method Q or blank
ATEX (European) II 1 G Ex ia IIC T5 Ta = -40°C to 70°C - 38343; Enty
Enty Parameters: U
i
= 15 V dc, I
i
= 60 mA, P
i
= 225 mW, C
i
= 0.3 μF, L
i
= 0 mH.
Canadian IS / I,II,III / 1 / ABCDEFG / T5 Ta = -40°C to 70°C - 38343; Enty
I / 0 / Ex ia / IIC / T5 Ta = -40°C to 70° C - 38343; Enty
(Non-incendive) NI / I / 2 / ABCD / T5 Ta = -40°C to 70°C
Enty Parameters: V
Max
= 15 V dc, I
Max
= 60 mA, P
i
= 225 mW, C
i
= 0.3 μF, L
i
= 0 mH
United States IS / I,II,III / 1 / ABCDEFG / T5 Ta = -40°C to 70°C - 38343; Enty
I / 0 / AEx ia / IIC / T5 Ta = -40°C to 70°C - 38343; Enty
(Non-incendive) NI / I / 2 / ABCD / T5 Ta = -40°C to 70°C
S / II,III / 2 / FG* / T5 Ta = -40°C to 70°C
*Class II and III, Division 2 applies only to model numbers ending in a Q sux.
Enty
Parameters: V
Max
= 15 V dc, I
Max
= 60 mA, P
i
= 225 mW, C
i
= 0.3 μF, L
i
= 0 mH
IECEx Ex ia IIC T5 Ta= -40 °C to +70 °C - 35331; Enty
Enty Parameters: U
i
= 15 V dc, I
i
= 60 mA, C
i
= 0.3 μF, L
i
= 0 mH.
Performance Curves
Opposed
Excess Gain Beam Paern
1
10
100
1.0 m
3.3 ft
10 m
33 ft
100 m
330 ft
0.1 m
0.33 ft
E
X
C
E
S
S
G
A
I
N
DISTANCE
1000
Q45AD9 E/R
Opposed Mode
4.8 m
16 ft
6 m
20 ft
3.6 m
12 ft
2.4 m
8 ft
1.2 m
4 ft
0
0
50 mm
100 mm
150 mm
50 mm
100 mm
150 mm
0
2 in
4 in
6 in
2 in
4 in
6 in
DISTANCE
Q45AD9 E/R
Opposed Mode
Q45AD9 NAMUR Series Sensor
P/N 38343 Rev. K www.bannerengineering.com - Tel: +1-763-544-3164 5