Models are available with either a 2 m (6.5 ) or 9 m (30 ) long aached PVC-covered cable, or a 4-pin M12/Euro-style quick
disconnect (QD) connector. Quick disconnect models (with Q in the model number sux) use MQD9-4.. mang cable (either straight or
right angle connector; see Accessories on page 9). Contact Banner Engineering for the availability of sensor models with 9 m (30 )
long aached cable.
Installaon Instrucons
Ex/HazLoc Applicaons
WARNING:
Explosive Atmospheres/Hazardous Locaons
The user has the responsibility to ensure that all local, state, and naonal laws, rules, codes, or regulaons
relang to the installaon and use of this Banner device in any parcular applicaon are sased. This
Banner device must be installed by Qualied Persons, in accordance with this document and applicable
regulaons.
A Qualied Person is a person who, by possession of a recognized degree or cercate of professional
training, or who, by extensive knowledge, training and experience, has successfully demonstrated the
ability to solve problems relang to the subject maer and work.
WARNING:
Explosion Hazard
Do not disconnect equipment unless the power has been switched o or the area is known to be non-
hazardous.
CAUTION: Electrostac Discharge (ESD)
Special Condions for Safe Use. Parts of the enclosure are non-conducng and may generate an ignion-capable
level of ESD. Cleaning of the equipment shall be done only with a damp cloth.
General Notes and Condions for Safe Use:
See Specicaons and Wiring Diagrams for important informaon concerning enty parameters, permissible locaons,
electrical connecons and cercaons.
In addion to the warning above concerning user responsibility, the installaon must comply with the following:
All installaons must comply with all manufacturer's instrucons.
U.S. Installaons: The relevant requirements of the Naonal Electrical Code
®
(ANSI/NFPA-70 (NEC
®
) and when
appropriate ANSI/ISA-RP12.06.01 Installaon of Intrinsically Safe Systems for Hazardous (Classied) Locaons.
Canadian Installaons: The relevant requirements of the Canadian Electrical Code (CSA C22.1).
ATEX and IECEx Installaons: The relevant requirements of EN 60079-14 and applicable Naonal regulaons.
Do not aempt any repairs to this Banner device; it contains no eld-replaceable parts or components. Tampering and/or
replacement with non-factory components may adversely aect the safe use of the system.
Approved Apparatus enty parameters must meet the following requirements:
V
oc
or V
t
V
max
C
a
C
i
+ C
cable
I
sc
or I
t
I
max
La L
i
+ L
cable
Sensor
Enty Parameters:
V
max
(Ui) 15 V dc
I
max
(li) 60 mA
P
i
225 mW
C
i
= 0.3 μF
L
i
= 0 mH
Cable
Enty Parameters (if unknown):
C
cable
= 60 pF/
L
cable
= 0.2 µH/
The ambient operang temperature range of the Sensors is 40 °C to +70 °C (40 °F to +158 °F).
For U.S. installaons, Class II and III, Division 2 applies only to model numbers ending in a Q sux.
For intrinsically safe installaons, sensors must be used with cered intrinsically safe switching ampliers and barriers
(Approved Apparatus) with intrinsically safe circuits that limit supply voltage and current in the event of failures.
Associated Apparatus is not required for
installaon of the devices within a Division 2 hazardous (classied) locaon when
installed per the Naonal Electrical Code. The maximum voltage for Division 2 installaon is 15V dc. In Division 2 installaons
(without Associated Apparatus), observe Explosion Hazard warning at the beginning of this secon.
Associated Apparatus is not required for installaon of the devices within a Division 2 hazardous (classied) locaon when
installed in, or through the wall of a suitable enclosure with provision for connecon of rigid metal conduit per the Canadian
Electrical Code, as acceptable to the local inspecon authority having jurisdicon. The maximum rang for Division 2
installaon is 15V dc, 60 mA. In Division 2 installaons (without Associated Apparatus), observe Explosion Hazard warning at
the beginning of this secon.
Maximum non-hazardous area voltage that the Approved Apparatus (intrinsically safe circuit) is connected to must not exceed
250V.
Q45AD9 NAMUR Series Sensor
P/N 38343 Rev. K www.bannerengineering.com - Tel: +1-763-544-3164 3
购买、咨询产品请填写询价信息:(3分钟左右您将得到回复)
询价型号*数量*批号封装品牌其它要求
删除
删除
删除
删除
删除
增加行数
  •  公司名:
  • *联系人:
  • *邮箱:
  • *电话:
  •  QQ:
  •  微信:

  • 关注官方微信

  • 联系我们
  • 电话:13714778017
  • 周一至周六:9:00-:18:00
  • 在线客服:

天天IC网由深圳市四方好讯科技有限公司独家运营

天天IC网 ( www.ttic.cc ) 版权所有©2014-2023 粤ICP备15059004号

因腾讯功能限制,可能无法唤起QQ临时会话,(点此复制QQ,添加好友),建议您使用TT在线询价。

继续唤起QQ 打开TT询价