Fusetron™ 600V Class RK5
FRS-R — 600 Vac/300 Vdc, 65-600 A, dual element, time-delay fuses
Catalog symbol:
•
FRS-R-(amp)
Description:
Advanced protection, energy efficient Class RK5
dual element, current-limiting, time-delay fuses.
Time-delay – 10 seconds (minimum) at 500% of
rated current.
Specications:
Ratings
•
Volts — 600Vac, 300Vdc
•
Amps — 65-600A
•
Interrupting rating
• 200 kA Vac RMS Sym
• 20 kA Vdc
Agency information
•
UL
®
Listed, Std. 248-12, Class RK5, Guide
JDDZ, File E4273
•
CSA
®
Certified, C22.2 No. 248.12, Class
1422-02, File 53787
•
CE
Catalog numbers (amps)
FRS-R-65 FRS-R-125 FRS-R-350
FRS-R-70 FRS-R-150 FRS-R-400
FRS-R-75 FRS-R-175 FRS-R-450
FRS-R-80 FRS-R-200 FRS-R-500
FRS-R-90 FRS-R-225 FRS-R-600
FRS-R-100 FRS-R-250
FRS-R-110 FRS-R-300
Carton quantity
Amp ratings Carton Qty.
65–100 1
101–200 1
201–400 1
401–600 1
Features:
•
Provides motor overload, ground fault
and short-circuit protection. When used in
circuits subject to surge currents such as
those caused by motors, transformers and
other inductive components, these fuses
can be sized close to full-load amps to give
maximum overcurrent protection
•
The time-delay feature makes it possible
to use fuse amp ratings which are much
smaller than those of non-time delay
fuses. Considerable cost saving occurs by
permitting the use of smaller size switches,
panels and fuses themselves
•
Provides a good degree of short-circuit
protection (greater current-limitation) to help
protect downstream components from high
fault currents
•
Gives motor running back-up protection to
motors without extra cost
•
Helps protect motors against burnout from
overloads and single-phasing when sized
properly
•
Simplifies and improves blackout prevention
(selective coordination ratios)
•
Dual-element fuses can be applied in
circuits subject to temporary motor
overloads and surge currents to provide
both high-performance, short-circuit and
overload protection
Dimensions - in:
A
B
Amp ratings A B
65-100 7.88 1. 11
110-200 9.63 1.61
225-400 11.63 2.34
450-600 13.38 2.88
Technical Data 1018
Effective May 2016
Supersedes July 2013
BUSSMANN
SERI ES