Technical Data 1017
Effective August 2018
Supersedes May 2016
Fusetron™ 600 V Class RK5 FRS-R — 600 Vac/300 Vdc,
1/10-60 A, dual element, time-delay fuses
Catalog symbols:
•
FRS-R-(amp) (non-indicating)
•
FRS-R-(amp)ID (indicating)
Description:
Advanced protection, energy efficient Class RK5
dual-element, current-limiting, time-delay fuses
with optional open fuse indication on select
ratings. Time-delay — 10 second (minimum) at
500% of rated current.
Specifications:
Ratings
•
Volts
• 600 Vac, 300 Vdc (1/10-30 A)
• 600 Vac, 250 Vdc* (35-60 A)
•
Amps — 1/10-60 A
•
Interrupting rating
• 200 kA Vac RMS Sym
• 20 kA Vdc
* Indicating versions not Vdc rated.
Agency Information
•
UL
®
Listed, Std. 248-12, Class RK5,
Guide JDDZ, File E4273
•
CSA
®
Certified, C22.2 No. 248.12,
Class 1422-02, File 53787
•
CE
Catalog numbers (amps)
FRS-R-1/10 FRS-R-1 8/10 FRS-R-8*
FRS-R-1/8 FRS-R-2 FRS-R-9*
FRS-R-15/100 FRS-R-2 1/4 FRS-R-10*
FRS-R-2/10 FRS-R-2 1/2 FRS-R-12*
FRS-R-1/4 FRS-R-2 8/10 FRS-R-15*
FRS-R-3/10 FRS-R-3 FRS-R-17 1/2*
FRS-R-4/10 FRS-R-3 2/10 FRS-R-20*
FRS-R-1/2 FRS-R-3 1/2 FRS-R-25*
FRS-R-6/10 FRS-R-4 FRS-R-30*
FRS-R-8/10 FRS-R-4 1/2 FRS-R-35*
FRS-R-1 FRS-R-5 FRS-R-40*
FRS-R-1 1/8 FRS-R-5 6/10 FRS-R-45*
FRS-R-1 1/4 FRS-R-6* FRS-R-50*
FRS-R-1 4/10 FRS-R-6 1/4* FRS-R-60*
FRS-R-1 1/2 FRS-R-7*
FRS-R-1 6/10 FRS-R-7 1/2*
* Open fuse indication available by inserting the suffix “ID.”
E.g., FRS-R-15ID. 35 to 60 amp indicating fuses are not
Vdc rated.
Carton quantity
•
10
Features and benefits
•
Dual-element feature provides the best time-
delay performance, allowing closer sizing and
superior protection of motors and transformers
•
Closer sizing allows for smaller fuses and less
costly switches
•
Class RK5 fuses with a 200 kA interrupting rat-
ing for use in a broad range of applications
•
Provides motor overload, ground fault, and
short-circuit protection
•
Helps protect motors against burnout from
overloads and single-phasing when sized prop-
erly
•
Dual-element fuses can be applied in circuits
subject to temporary motor overloads and surge
currents to provide both high performance
short-circuit and overload protection
•
Offers a 10-second time delay at 5 times the
rated current
•
The time-delay feature makes it possible to use
fuse amp ratings that are much smaller than
those of non-time delay fuses. Considerable
cost savings occur by permitting the use of
smaller size switches, panels, and fuses them-
selves.
•
Provides current limitation to help protect down-
stream components from high fault currents.
•
Gives motor running back-up protection to
motors without extra costs.