DC Series
DC Series
RFI Power Line Filters for DC Applications
217
Corcom Product Guide
DC Filters
4
Hipot rating (one minute):
Line to Ground: 2250 VDC
LIne to Line: 1450 VDC
Rated Voltage (max): 80 VDC
Rated Current: 15 to 125A
Operating Ambient Temperature Range
(at rated current I
r
): -10°C to +55°C
In an ambient temperature (T
a
) higher than +55°C
the maximum operating current (I
o
) is calculated as
follows: I
o
= I
r
(85-Ta)/30
UL Recognized
CSA Certified
TUV Certified
• General purpose line filters for DC applications up
to 125VDC
• Available with or without a circuit breaker
• Available with feedthrough capacitors for added
high frequency performance
• Available in both flange mound (DCF) and
bulkhead mount (DCB) configuration
Ordering Information
60 DC B 6 B
Options
B – Circuit breaker
F – Feedthrough capacitors
BF – Circuit breaker and
feedthrough
F and BF available only in
bulkhead (B) mounting style
Omit for none
I
nput / Output Styles
6 – Redundant stud
10 – Phoenix terminal
M
ounting Style
F = Flange
B = Bulkhead and rack
Required for F or BF options
DC Series
Current Rating
15, 30, 60, 100 or 125A
Specifications
Electrical Schematics
Note 1
Note 2
Note 3
Note 4
Note 1
LINE
LOAD
EN
60 950
60DCF6B 15DCF10
Note 3
Note 2
Note 4
Note 1
LINE
LOAD
Dimensions are in inches and millimeters unless otherwise specified. Values in italics
are metric equivalents. Dimensions are shown for reference purposes only.
Specifications subject to change.
Catalog: 1654001
Issue Date: 06.2011
For email, phone or live chat, please go to
te.com/help
corcom.com
Standard Performance
High Frequency Performance
(F & BF Styles)