http://www.m-system.co.jp/ 10BXC SPECIFICATIONS ES-0893 Rev.12 Page 2/7
Power RUN LED: Light turns on in normal conditions
(supplied only with dual-redundant power supply or two
independent power sources)
OUTPUT SPECIFICATIONS
■ Alarm Output
(Supplied only with dual-redundant power supply or two
independent power sources)
Rated load: 250 V AC @ 3 A (cos ø = 1)
30 V DC @ 3 A (resistive load)
Maximum switching voltage: 250 V AC or 125 V DC
Maximum switching power: 750 VA or 60 W
Minimum load: 5 V DC @ 100 mA
Mechanical life: 5 × 10
6
cycles (rate 180 cycles/min.)
INSTALLATION
Supply pressure: Refer to the data sheet for I/P transducers
(power distribution & pressure supply type)
Power consumption
•AC: 130 VA min.
•DC: 2.5 A min.
Operating temperature: -5 to +55°C (23 to 131°F) 0 to 50°C
(32 to 122°F) for AC power
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: JIS or EIA standard rack
Weight
Single power supply w/o power units:
3.0 kg (6.6 lb) with DC power type
3.5 kg (7.7 lb) with AC power type
Dual-redundant or two independent power sources:
3.5 kg (7.7 lb) with AC/DC power type
4.0 kg (8.8 lb) with AC/AC power type
Add 2 kg (4.4 lb) for air manifold type.
PERFORMANCE
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute (I/O connector to
alarm output to power)
1500 V AC @ 1 minute (power to FG)
500 V AC @ 1 minute (I/O connector or alarm output to FG,
1000 AC with power input code R)
Maximum supply pressure: 196 kPa
(2 kgf/cm
2
, 1.96 bar, 28 psig)