13
ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de
1
PTC-resistor relays type MS
Technical Data
MS220K2
PTC-Resistor-Relay Type MS(R)220K2
2 PTC-Circuits
•
•
•
•
•
•
•
MSR220K2
Rated supply voltage US
connectable PTC resistors
switching point
output relays
type of contact
test conditions
rated ambient temperature
range
dimensions (h x w x d) attach-
ment
protection housing / terminals
weight
AC 230 V, ± 10 %, 50/60 Hz, ≤2 VA
AC/DC 24 V, AC ± 10 %, DC 21-30 V, < 2 VA,
without potential separation
2 x 1... 6 PTC according to DIN 44 081 or 44 082
<4000 Ω
2 x 1 change-over contact (co)
type 2 (see "general technical informations")
see "general technical informations"
-20...+55 °C
design K: 75 x 22.5 x 110 [ mm ]
on 35 mm DIN rail according to DIN EN 50 022
or with screws M4 (option)
IP 30 / IP 20
approx. 145 g
Same execution as MS220K
2, additionally with electronic
reclosing lock:
electronoic reclosing lock
(disconnectible)
integrated RESET-button
link for external RESET
automatic RESET at voltage
recovery
Order numbers:
AC/DC 24 V T221943
AC 230 V T221945
The MS220K2 monitors 2 PTC-
resistor sets at the same time. If
a temperature rise occurs in one
set, the appropriate output relay
releases.
With this relay, 2 PTC-sets can
be independently monitored on
only 22.5 mm space
2 PTC-resistor sets, each 1...
6 PTC resistors
output relays 2 x 1 change-
over contact (co)
LEDs for operation and
alarm
Order numbers:
AC/DC 24 V T221923
AC 230 V T221925
2015-12-11
A1
A2
14 12
24
22 T0
T1
T2 Y1
Y2
11
Us
M 3
1-6 PTC
M 3
1-6 PTC
F5-F7 F1-F3
K2 K1
S31)
H2H1
F4
S1
S4
S2 S5
K1 K2
K1 K2
L2
L3
1)
1)
Ue : 250 V
I
e : 3 A
AC 15
N
+
~
–
~
Us = Anschlussspannung
S2, S5 = Ein - Taster
H1, H2 = Störmeldung
K1, K2 = Motorschütz
S1, S4 = Aus- Taster
S3 = Externer Reset
F1 - F8 = Sicherung
1) nur MSR