ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de
Monitoring of over- and undervoltage 40…520 V
monitoring of over- and underfrequency 45…65 Hz
monitoring of quality of voltage (10-minutes-average)
monitoring of vector-shift 2…20 °, 1 or 3-phase
Switching-delay adjustable <0,05…60,0 s
Switching-back-delay adjustable 0…1000 s
Alarm-counter for up to 100 alarms (with measured
value and reason)
Added time of alarm up to 999 hours. Displays the
time, alarms have been active (while supply voltage
applied only)
LEDs for alarms, allocation of values and states of
relays
2 output-relays, each for monitoring frequency and/
or voltage
function of relays (nc- or no -operating mode) pro-
grammable
interlocked switching or autoreset
input for Enable / Reset
easy programming by help of basic programs
Sealing of settings is possible
code-lock against manipulation of settings
universal power-supply AC/DC 24-270 V
housing for DIN-rail-mount, 70 mm wide, mounting
height 66 mm
Voltage Monitoring Type UFR
Voltage- and Frequency Relay UFR1001
with integrated vector shift relay, sealable
The voltage- and frequency relay
UFR1001 monitors voltage and
frequency in two- or three-phase
networks with or without neutral
and switches o rapidly when
required.
The device can be easily adapted
to the requirements of the carrier
of the power network.
With the integrated vector-step
relay it can also monitor networks
at synchronous generators.
After selecting a basic program,
for each relay limits can be
programmed for over-/undervol-
tage and over-/underfrequency.
In programs with vector-step-
monitoring, K2 is used for vector-
step only.
Applications are monitoring
power-networks at great solar-
plants, in block power heating
stations, also with synchronous
generators (vector shift) or ge-
nerally monitoring the quality in
power networks at machines or
power-supplies.
2015-01-30
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
UFR1001