124
ZIEHL industrie-elektronik, 74523 Schwäbisch Hall, Germany, +49 791 504-0, info@ziehl.de, www.ziehl.de
MINIPAN 352V
Universal-Instrument MINIPAN 352V
for DIN-rail-mounting
Measuring of resistance:
Range 0...500 Ω
Range 0...30 kΩ
Easy programming with 3 buttons and supporting
display:
Display (zero, fullscale, decimal point)
2 switching points with hysteresis and delays
EasyLimit for easy setting of alarms
Switching with automatic reset or interlocked
MIN/MAX-contacts or operating-/closed cur-
rent mode of relays
Storage of MIN- and MAX-values
Average of multiple measurings
Simulation of operation
Code-lock against manipulation of settings
Outputs 2 potential-free change-over contacts
(co)
Supply-voltage for external measuring transducer
4-20 mA
Sticker with dierent measuring units included
Terminals pluggable
Mounting dimensions 72x72 mm
Supply-voltage AC/DC 24-240 V
Option: analog output 4...20 mA (insulated when
externally supplied)
With its 4 digit, 14 mm high display,
Digital Panelmeters of MINIPAN
352V- series allow the accurate
display of dierent values in the
range -1999 ... +9999.
Measuring inputs AC (True
RMS), DC current and voltage
and measuring of restistance
and of temperatures with various
sensors are combined in one
instrument.
Two programmable switching
points allow applications as
limit-switch or 2- or 3-point con-
troller.
With EasyLimit the switching
points can be set easily. Other
parameters are blocked and
thus protected from unindended
manipulation.
With its analog output (option)
it is in addition a measuring-
transducer.
The display can be easily pro-
grammed by the user (e.g. input
DC 4-20 mA / display 0-350.0 m/s
or 0...200 Ω / 0...3000 mm or AC
0-5 A / 0-400.0 A).
In addition the built-in universal
power-supply AC/DC 24-240 V
makes it even more versatile.
Temperature:
Pt 100 (RTD) , Pt 1000,
KTY 83 and KTY 84 in 2- or
3-wire connection
Thermocouples type B, E,
J, K, L, N, R, S, T
Measuring range –170 ...
+1820 °C
Resolution 0.1 °C (up to
999.9 C)
Display in °C or °F
AC/DC-measuring inputs:
300 mV for measuring
current with external
shunt
1 and 5 A for direct measu-
ring of current (or AC with
external transformer)
500 V
10 V for standard signals
20 mA for standard si-
gnals
AC-measuring TrueRMS
•
•
•
•
•
•
•
•
•
•
•
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2011-01-30
MINIPAN 352V
Part numbers:
D340101
D340110 with analog output