Surge Arrester A83-A170X
2-Electrode-Arrester Ordering code: B88069X4360C102
AB E / AB PM Issue 01, 19.02.2003
Page 1 of 2
DC spark-over voltage
1) 2)
170
± 20
V
%
Impulse spark-over voltage
at 100 V/µs - for 99 % of measured values
- typical values of distribution
at 1 kV/µs - for 99 % of measured values
- typical values of distribution
< 650
< 500
< 800
< 600
V
V
V
V
Nominal impulse discharge current (wave 8/20 µs)
Single impulse discharge current (wave 8/20 µs)
10
20
kA
kA
Nominal alternating discharge current (50 Hz, 1 s)
Alternating discharge current (50 Hz, 9 cycles)
20
100
A
A
Insulation resistance at 100 V
dc
> 10
GΩ
Capacitance at 1 MHz < 1.5 pF
Arc voltage at 1 A
Glow to arc transition current
Glow voltage
~ 10
~ 0.5
~ 95
V
A
V
Weight ~ 2.5 g
Operation and storage temperature -40 ... +90 °C
Climatic category (IEC 60068-1) 40/ 90/ 21
Marking, red
170 YY O
170 - Nominal voltage
YY - Year of production
O - Non radioactive
1)
At delivery AQL 0.65 level II, DIN ISO 2859
2)
In ionized mode
Terms in accordance with ITU-T Rec. K.12 and DIN 57845/VDE0845