101
Three Phase Filters
2
• Designed for very high insertion loss for Delta
three phase, three wire applications
• Available with common or differential mode coils
Ordering Information
100 ADT 6 S
Suffix
S – Differential mode coils
Omit if none
I
nput / Output Style
6 – Threaded bolt
A
DT Series
Current Rating
63, 100, 160 or 200A
Specifications
Electrical Schematics
A
B
C
A
B
C
63ADT6
UL Recognized
Available Part Numbers
63ADT6 63ADT6S
100ADT6 100ADT6S
160ADT6 160ADT6S
200ADT6 200ADT6S
Dimensions are in inches and millimeters unless otherwise specified. Values in italics
are metric equivalents. Dimensions are shown for reference purposes only.
Specifications subject to change.
Corcom Product Guide
Catalog: 1654001
Issue Date: 06.2011
For email, phone or live chat, please go to
te.com/help
corcom.com
High Performance High Current 3-phase Delta RFI Filters
ADT Series
ADT Series
Maximum leakage current at 277 VAC 60 Hz,
each Line to Ground:
ADT6: 1.3 A
63ADT6S: 2.6 A
100, 160, 200ADT6S 4.6 A
Hipot rating (one minute):
Line to Ground: 2210 VDC
Line to Line: 2158 VDC
Rated Voltage (max):
Phase to Phase: 480 VAC
Phase to Ground: 277 VAC
Operating Frequency: 50/60 Hz
Rated Current: 63 to 200A
Operating Ambient Temperature Range
(at rated current I
r
): -10°C to +40°C
In an ambient temperatu
re
(T
a
) higher than +40°C
the maximum operating current (I
o
) is calculated as
follows: I
o
= I
r
(85-Ta)/45